I Purpose
¡õ¡õRKG-¡õ¡õ¡õ¡õ¡õ model thermal control cabinet of attemper and reducer
device is autocontrol device assembled with attemper and reducer£¨or
attemper device and reducer device£©, which can conduct autocontrol
or manual remote control on board towards attemper and reducer device£¨or
attemper device and reducer device£© and enables its secondary parameters
£¨temperature and pressure£©to reach requirements of production process.
Attemper and reducer device and its thermal control cabinet are
widely used in industries of textile, petro-chemistry and power
station.
II Application Capabilities
¢ñ.Temperature
1. Reading accuracy of inlet and outlet steam temperature is not
less than 1.0 grade£»
2. Recording accuracy of outlet steam temperature is not less than
1.5 grade£»
3. Static difference of temperature adjusting system of outlet steam
temperate is not more than 1.5%.
¢ò.Pressure
1.Reading accuracy of inlet and outlet steam pressure is not less
than 1.0 grade£»
2.Recording accuracy of outlet steam pressure is not less than 1.5
grade
3.Static difference of pressure adjusting system of outlet steam
temperate is not more than 1.0%.
¢ó.Flow
Reading accuracy of steam flow and cooling water flow is not less
than 1.5 grade£»
Cumulate calculation accuracy of steam flow and cooling water flow
is not less than 1.5 grade.
¢ô.Alarm
Setting range of outlet steam temperature and pressure alarming£º
1.Upper limit is 10¡«100% of the full range£»
2.Lower limit is 0¡«90% of the full range.
¢õ.Repsonse Time£º
1.Autocontrol£ºresponse time of adjusting system¡Ü2S£»
2.Manual operation on board£ºcontrol valve changing from full shutting
to full opening£¨from full opening to full shutting£©takes at least
25S¡À20%£¨special requirements should be otherwise negotiated£©.
III Supply Range
Supply range of thermal control cabinet are£º
1.All instruments and electric components installed on instrument
panel of thermal control cabinet£¨including adjuster, controller,
memorizing meter, shower, flow calculator, signal lamp, power source
switch and button etc.£©.
2.All instruments and electric components installed below instrument
panel of the thermal control cabinet£¨there are servo amplifier,
power source cabinet, distributor and automatic switch etc.£©.
3.All test components installed on spot£¨including thermal couple,
remote pressure meter, temperature transmitter, pressure transmitter,
speed equalizer or orifice plate and differential pressure transmitter
etc.£©.
4.Executive framework installed on spot£ºelectric performer£¨or pneumatic
performer£©.
Customer only needs to add the following installatioin materials£º
1.Interface of thermal couple with specification of M27¡Á2£ºtwo pieces
of attemper and reducer device£¨inlet and outlet pipelines each£©£»a
piece of reducer device£¨fixed on inlet pipeline£©. Meters of compensation
lead of thermal couple£¨graduation number of£ºE£©.
2.Guide pressure lead, interface and needle valve£ºouter diameter
of guide pressure pipe ¦Õ14, diameter ¦Õ6¡«¦Õ10£¨subject to value of
pressure£©£»interface screw of instrument guide pressure M20¡Á1.5£¨attemper
and reducer device, two for reducer device and one for attemper
device£©.
3.Connecting lever and pin between performer and lever of adjusting
valve£¨specification diverges according to different installation
positions£©. It needs two pieces of attemper and reducer device£»or
only one for attemper device and reducer device each.
4.Installation tube of temperature transmitter and pressure transmitter£¨with
specification of ¦Õ50£©£ºtwo for attemper and reducer device£»and only
one for attemper device or reducer device each£¨for additional flow
test device£ºone more for DL£»and two more for SL£©. Ground feet bolts
M12 of performer installation£»£¨4 for reducer part of attemper and
reducer device£©8 for attemper and reducer device£»and only 4 for
attemper device or reducer device. And some ground feet bolts of
thermal control cabinet installation£¨specification or number can
refer to chart I, chart II or chart III£©. Meters of control wire£¨number
of electric core cable can refer to chart I, chart III or chart
V£©.
IV Ordering Notice
¢ñ¡¢ When ordering please indicate£º
1. Model of thermal control cabinet£»
2. Steam parameters Q, P1, P2, t1, t2 and parameters of cooling
water Pb, tb.
3. Color code £¨thermal control cabinet of our factory is generally
produced according to international G01 apple green. If customer
needs other colors, such as Y01 camel grey color and Y02 pearl color
etc, please note in addition£©.
4. Customer who orders additional flow test device needs to offer
P2max, P2const, P2min, t2max, t2const and t2min in addition if P2
and t2 need to be changed to improve calculation accuracy in course
of use.
¢ò¡¢ If having special requirements, please indicate after negotiation
or sign other technical agreement.
V Other
1. Installation and debugging of thermal control cabinet are in
the charge of users £¨or installation company£©. If needing our helps
on debugging and trial production, debugging expenses should be
charged considerably.
2. We also assume research and production of all new types of instrument
thermal control cabinet and complete device business of automatic
control system of industries of power station, petro-chemistry and
textile etc, which can be ally design and processing with offered
drawings. Welcome to negotiate and place orders.
VI Theory Chart of Control System


>Previous |